Sound Insulation Testing & Ventilation Testing

THE BRIEF

  • To pass an Airborne test for new build properties you must score 45db or higher 
  • Airborne tests measure the difference in sound levels between the receiver room and neighbouring walls or floors
  • If the sound output in the receiver room is 100db and the sound leakage being passed through into the neighbouring room is 40db, then the result would be 60 and therefore would be a pass
Sound Testing & Ventilation Testing

THE PROCESS

  • After our technicians calculated the areas of the apartments on site, testing was ready to be carried out. All calibrated equipment was setup in accordance to our strict procedures to ensure the most accurate result possible

THE RESULTs

  • SOUND TESTING RESULTS

Airborne Wall Target

≥ 45

Plot 32a Living Room - Plot 32 Living Room

≥ 45

Plot 32a Bedroom - Plot 32 Bedroom

Airborne Wall Result

50

Plot 32a Living Room - Plot 32 Living Room

59

Plot 32a Bedroom - Plot 32 Bedroom

PASS

PASS

  • Compliant
  • All the Ventilation Tests passed with no problems
  • We achieved a Water Efficiency Rate of 109.65 Litres per person per day, the Target being ≤ 110L  
  • Our Combined Testing package offers excellent value  

For further guidance, please refer our How To Guides in our Advice Centre here